Energy meter KLEFR 6944 – 3 Ph. CT MID Modbus

Energy meter KLEFR 6944 – 3 Ph. CT MID Modbus

Product Code: KLEFR-6944
Availability: 4
  • 149.00€

  • 10 pcs: 135.00€
  • 30 pcs: 119.00€

Available Options




KLEFR and Inepro meters are interchangeable

Three phase CT connected energy meter

The KLEFR 6944 is a high quality three phase CT connected meter designed for applications like photovoltaic systems (PV), electric vehicle chargers (EV) and building management systems (BMS). Due to its compact size (4 DIN Module) and easy installation, integration and configuration, the meter will fit in every PV, EV and BMS application that requires (MID) metering.

MID approved

All KLEFR meters comply with the Measuring Instruments Directive 2014/32/EU. The MID approval ensures the accuracy and quality of the meter and enables its use in billing purposes. The KLEFR 694x is measuring active energy with accuracy class B (=1) and reactive energy with accuracy class 2. The certificates and other meter specifications can be found in the user manual.

Communication

Data from the KLEFR meters can be collected and programmed via the M-bus, Modbus or Infrared interface. The KLEFR 6943 meter has a built in M-bus interface for communication. The KLEFR 6944 can communicate and be programmed via the Modbus RTU (RS-485) interface. All KLEFR meters are equipped with an Infrared interface (for reading and programming) and a selectable pulse output. More information like the Modbus register map, M-bus specifications and infrared user manual can be found in the 694x user manual.

Display pages

Navigation through the display pages of the KLEFR 694x can easily be done by using the arrow shaped buttons on the front of the meter. Information like the meter serial number, current direction, various settings and the following values can be displayed on the LCD:

Settings

Settings can be done manually and with a Modbus, M-bus or Infrared command. The settinegs can be checked in program mode 1 and changed in program mode 2 or 3. The settings in program mode 3 are password protected.

  • Modbus/M-bus ID can be set to a value from 1 to 247 (Modbus) and 1 to 250 (M-bus).
  • Baud rate can be set to 1200, 2400, 4800 or 9600.
  • Modbus parity can be set to even, none or odd.
  • CT ratio has to be programmed before use.
  • Automatic scroll function can be customized by adding and deleting display pages.
  • LCD cycle time can be set to a scroll time from 1 to 30 seconds.
  • Backlight mode can be set to ON, OFF or Button mode.
  • S0 output can be set to 10.000/2.000/1.000/100/10/1/0,1/0,01 imp/kWh.
  • Calculation mode of the total active energy can be set to 01=forward only, 04=reverse only,
    xxx05=forward+reverse, 06=reverse-forward, 09=forward-reverse, 10=forward-reverse and
    xxx11=forward-reverse.
  • Power down counter can be reset to 0.
  • Password can be changed in program mode 3.
Environmental conditions
Operation temperature -25°C - +70°C
Storage temperature -30°C- +70°C
Relative humidity ≤ 75%
Electrical specification
Input power supply / Input voltage 230/400V AC (3~) [3*230/400V ±20%]
Basic current (Ib) 1,5A
Maximum rated current (Imax) 6A
Operational frequency range 45-60Hz
Accuracy class B (=1% accuracy)
Insulating encased meter of protective class II
RS485 communication specifications
Bus type RS485
Protocol MODBUS RTU with 16 bit CRC
Baud rate 1200, 2400, 4800 and 9600 (default)
Address range 1-247 user settable
Mechanical and enclosure specification
Product dimension (outline) 93mm(W) x70mm(D) x 63mm(H)
Mount type DIN Rail mountable
Enclosure material PC flame resistant plastic
Enclosure colour Light Gray
Product weight 400g (net)
Enclosure protection level IP51

Datasheets

Software Downloads

Title Version Date
KLEFR IR Software 171208 2023-05-15